礦物絕緣電纜的敷設時的注意事項

1、電纜在敷設前,均應檢查(cha)電纜是否(fou)完好,絕緣電阻是否(fou)達到(dao)標準(zhun)要(yao)求

2、電(dian)纜(lan)敷(fu)(fu)設(she)時,其固(gu)定(ding)點之(zhi)間的(de)間距,除支架敷(fu)(fu)設(she)在支架處固(gu)定(ding)外(wai),其余可按下表中(zhong)推薦(jian)的(de)數(shu)值固(gu)定(ding)在明敷(fu)(fu)部(bu)位,如果相同走向的(de)電(dian)纜(lan)大、中(zhong)、小(xiao)規格都有,從(cong)整齊、美觀方面考慮,可按zui小(xiao)規格電(dian)纜(lan)標(biao)準要求固(gu)定(ding),也可分(fen)檔距離固(gu)定(ding)。當電(dian)線傾斜敷(fu)(fu)設(she)時,電(dian)纜(lan)與垂直方向成30度(du)(du)及以下時,按垂直間距固(gu)定(ding);大于(yu)30度(du)(du)時,按水平間距固(gu)定(ding)。

3、電纜敷設(she)時,在轉彎處(chu)、中間連接器兩(liang)側,有條件(jian)固定的應(ying)加以(yi)固定。

4、計算(suan)敷設電(dian)纜所需長(chang)度時,應考慮留(liu)有1%的余量(liang)。

5、對電纜在運行中可能遭受(shou)到機械損傷的部位,應采取適(shi)當的保護措施。

6、單(dan)芯電(dian)纜敷設(she)時,應逐根敷設(she),待每組布(bu)齊(qi)并(bing)矯(jiao)直(zhi)后,再作排(pai)列(lie)綁扎(zha),綁扎(zha)間距以1一1.5M為宜。

7、有腐(fu)蝕作用的環境(jing)中敷(fu)設銅(tong)護(hu)套(tao)電纜時,或(huo)在部(bu)分埋地(di)或(huo)穿管敷(fu)設時,應采用聚氫(qing)乙烯外護(hu)套(tao)或(huo)低(di)煙(yan)無鹵外護(hu)套(tao)。

8、布線過程中,電纜據斷(duan)后應立(li)即對其端部進行臨(lin)時性密封(feng)。

9、電(dian)纜全長均為直線敷設或聯接(jie)用(yong)電(dian)器(qi)可能(neng)產生振動(dong)時,要(yao)在允許場(chang)合(he)設置膨(peng)脹(zhang)環。

10、一般礦物絕緣電纜(lan)無(wu)需(xu)穿(chuan)管敷(fu)設,特殊場合須穿(chuan)管(單芯(xin)電纜(lan)不允許單獨(du)穿(chuan)金(jin)屬(shu)管敷(fu)設)

11、可以(yi)埋地敷設,但zui好(hao)(hao)不要有中間接頭(tou),如無法避免(mian),則接頭(tou)外需做好(hao)(hao)防水處理(li)。

12、對于(yu)大截面(mian)單芯電(dian)(dian)(dian)(dian)(dian)纜(lan),用(yong)于(yu)交流(liu)(liu)電(dian)(dian)(dian)(dian)(dian)網(wang)時(shi)(shi)應(ying)采取渦流(liu)(liu)消(xiao)除(chu)措施,在(zai)(zai)交變電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)作(zuo)(zuo)用(yong)下銅護套上(shang)(shang)會形(xing)成(cheng)橫向渦流(liu)(liu),造成(cheng)能量損(sun)耗。當線(xian)路(lu)負荷大而需要兩組(zu)以上(shang)(shang)電(dian)(dian)(dian)(dian)(dian)纜(lan)時(shi)(shi),可按下圖的(de)(de)形(xing)式(shi)排列兩組(zu)或多組(zu)電(dian)(dian)(dian)(dian)(dian)纜(lan),但(dan)每(mei)組(zu)之間要留有(you)兩倍電(dian)(dian)(dian)(dian)(dian)纜(lan)外徑(jing)的(de)(de)距離,而且每(mei)組(zu)電(dian)(dian)(dian)(dian)(dian)纜(lan)連接線(xian)位(wei)置(zhi)應(ying)相同。此外,在(zai)(zai)電(dian)(dian)(dian)(dian)(dian)纜(lan)進配電(dian)(dian)(dian)(dian)(dian)箱(xiang)/柜(ju)時(shi)(shi),為固(gu)定電(dian)(dian)(dian)(dian)(dian)纜(lan)需在(zai)(zai)箱(xiang)柜(ju)的(de)(de)面(mian)板上(shang)(shang)打孔(kong),同樣為防止電(dian)(dian)(dian)(dian)(dian)纜(lan)在(zai)(zai)進箱(xiang)/柜(ju)的(de)(de)鐵皮面(mian)上(shang)(shang)產(chan)生渦流(liu)(liu),在(zai)(zai)箱(xiang)柜(ju)板面(mian)上(shang)(shang)應(ying)按下圖所示(shi)方(fang)式(shi)開孔(kong),或加墊非磁性材(cai)料的(de)(de)隔板固(gu)定電(dian)(dian)(dian)(dian)(dian)纜(lan),這種支(zhi)架(jia)一般采用(yong)鋁母線(xian)或銅母線(xian)加工(gong)制作(zuo)(zuo)、打孔(kong),當采用(yong)扁(bian)鋼或角鋼制作(zuo)(zuo)支(zhi)架(jia)時(shi)(shi),這時(shi)(shi)也應(ying)參照上(shang)(shang)述方(fang)法開孔(kong),以防渦流(liu)(liu)產(chan)生。

13、單芯電(dian)纜敷設時(shi)每路電(dian)纜之間留有不(bu)少(shao)于電(dian)纜外徑2倍的間隙,如不(bu)留間隙則應考慮載流量減(jian)少(shao)系數。